Free Shipping Across the USA — Worldwide Delivery Available!
PALM Parts Solution
AccountQuote

FAULT CODE LIBRARY

ACS880 Fault 3381 — Output phase loss

Is your ABB ACS880 drive tripping with Fault 3381 (Output phase loss)? Learn how to troubleshoot cable issues, test motor windings, check parameters, and resolve it fast.

Worldwide Shipping
Fast Dispatch
Warehouse Pickup
1-Year Warranty

In short

Is your ABB ACS880 drive tripping with Fault 3381 (Output phase loss)? Learn how to troubleshoot cable issues, test motor windings, check parameters, and resolve it fast.

Overview

ABB ACS880 Fault 3381 indicates that the drive has detected an Output Phase Loss. This means the drive’s internal control system has identified an interruption or a massive current imbalance in one or more of the phases leading to the motor (labeled U2, V2, and W2). When the current drawn across all three terminals is not symmetrical, or if current drops to near zero on any single phase while the other phases are active, the drive trips to prevent destructive single-phasing on the motor windings.

In standard operations, the ACS880 uses highly precise current transducers connected immediately after the IGBT inverter bridge. If the microprocessor detects that a phase is disconnected or that the current has fallen below the minimum detection threshold while running under load, it activates Fault 3381. This protective trip stops the output execution to defend both the drive's electrical components and the motor from overheating or winding failure.

Symptoms

When Fault 3381 occurs on an ABB ACS880 drive, the system will manifest several noticeable behaviors in the field:

  • Keypad Alert: The primary control panel (Assistant Control Panel) displays "Fault 3381" along with the description "Output phase loss."
  • Physical Red Indicator: The drive module's status LED turns solid or blinking red, indicating an active trip condition.
  • Immediate Coast-to-Stop: The motor immediately loses torque and coasts to a stop rather than following a planned ramped deceleration.
  • Audible Motor Noise: Prior to tipping, the AC motor might produce a loud, unusual humming or low-frequency vibration as it struggles to run on unbalanced current.
  • Intermittent Operations: The system may run fine at low speeds or low torque but trip immediately when ramping up or during heavy load changes.

Possible Causes

Understanding what triggers Fault 3381 speeds up the recovery process. The most common root causes include:

  • Loose Field Connections: Loose or improperly torqued physical wire connections on the drive's output terminals (U2, V2, W2) or within the motor terminal box.
  • Broken or Damaged Motor Cable: Conductor breakage inside the conduit, sheared insulation, or cable degradation over a long run.
  • Open Circuit in Motor Windings: An internal break or thermal damage within the motor's stator windings, creating an open-circuit path on one phase.
  • Faulty External Components: Broken contacts, worn points, or open terminals on field isolators, safety disconnect switches, output reactors, or sine filters installed between the drive and the motor.
  • Failed Output Contactor: If an output contactor is fitted for safety isolation, failed or carbonized contacts can prevent one of the poles from closing cleanly.
  • Mismatched Motor Size: Connecting an extremely small testing motor to a high-capacity drive. If the motor current is below the current transducer's resolution, the drive incorrectly assumes a phase has been lost.
  • Internal Drive Failures: Damaged current transducers on the drive's output phase circuits, or damaged IGBT gating circuits on the main power board.

Step-by-Step Troubleshooting

Follow these steps in sequence to isolate and resolve the issue safely and efficiently.

Step 1: Lockout/Tagout and Safety Preparation

Before opening any enclosures or touching connections, safely stop the machinery. Disconnect the main AC incoming power line to the drive. Implement your facility’s Lockout/Tagout (LOTO) procedures. Crucial Safety Warning: Wait at least 5 to 15 minutes (refer to your specific ACS880 frame manual) to allow the DC bus capacitors to discharge down to safe voltage levels (< 50 VDC). Use a properly rated digital multimeter to verify the absence of voltage on the raw physical inputs and output terminals.

Step 2: Inspect Output Cable Terminals

Visually inspect and mechanically test the connections. Use a calibrated hand torque wrench to check the terminals on the drive (U2, V2, W2) as well as the connection lugs in the motor junction box. Look for signs of carbon tracking, pitting, terminal degradation, or excessive heat/discoloration on the wire insulation, which signals a high-resistance joint.

Step 3: Test Intermediate Devices and Contractors

If your setup features a local safety disconnect switch, an output contactor, or dynamic filtering (like a sine filter or du/dt reactor), evaluate them:

  1. Manually actuate contactors or safety local isolators to check for smooth mechanical action.
  2. Measure the contact resistance across each phase pole. Pitted contacts will show high or erratic ohm readings. Replace the switch or contactor if any pole shows high resistance (>0.5 ohms).

Step 4: Perform Motor & Cable Windings Isolation and Continuity Tests

Disconnect the motor cable leads entirely from the U2, V2, and W2 terminals on the bottom of the ACS880 drive to protect the internal silicon components before conducting high-voltage checks.

  1. Winding Balance Check: Using a standard digital multimeter set to a low-ohm range, measure the phase-to-phase resistance of the motor and cables together (U-V, V-W, W-U). The values should be extremely close (usually within a fraction of an ohm). An open circuit or unusually high resistance on one pair indicates a bad line or a damaged stator winding.
  2. Insulation Resistance (Megger) Test: Use a 500V or 1000V megohmmeter to test each line against the system ground wire. Ensure the readings are well within acceptable limits (typically greater than 100 Megohms). A grounded phase can trigger balance faults before registering as a hard ground fault.

Step 5: Test the Motor Directly

If the cable tests return questionable results, bypass the cable run. Perform the winding resistance checks directly at the motor junction box terminal strip. If the readings at the motor are completely balanced, the issue lies in the cable run between your panel and the motor.

Step 6: Perform a No-Load Drive Test

To determine if the fault is coming from inside the drive control housing:

  1. Disconnect the motor cable from the drive completely.
  2. Go to Parameter 31.19 Motor phase loss and temporarily change it to No action or Warning to prevent the drive from tripping without a load.
  3. Spin up the drive to a modest test frequency (e.g., 20Hz or 30Hz).
  4. Measure the output line-to-line voltage (U2-V2, V2-W2, W2-U2) at the drive's terminals using your multimeter. Note: You must use a multimeter equipped with a hardware-based low-pass filter (VoIP/VFD mode) to get an accurate, filtered RMS reading on a PWM waveform.
  5. If the outputs are not balanced within 1-3 volts of each other, the drive's output power module (IGBT) or gate driver board has likely failed.
  6. Important: Remember to change Parameter 31.19 back to its original safety setting (Fault) once testing is complete.

Based on your troubleshooting findings, execute the appropriate correction path:

  • If loose connections were found: Reconnect, clean the contact surfaces with electrical contact cleaner, and torque the lugs according to the specification manual for your ACS880 frame size.
  • If motor windings are unbalanced: Send the AC motor to an authorized motor service shop for rewinding or swap it out with a replacement unit.
  • If the cable insulation is compromised: Pull new, high-quality VFD-shielded cabling through the conduit.
  • If contactors are worn: Replace the offending contactor or safety isolator swap switch.
  • If the drive fails the no-load voltage test: Swap the internal power module assemblies or proceed to replace core internal components.

When parts require physical replacement, use original components to maintain system certification:

  • VFD-Rated Cables: Use symmetrically shielded motor cables to mitigate high-frequency currents and common-mode noise issues.
  • Output Contactors / Disconnects: Spec-matched heavy-duty contactors rated for AC-3 inductive loads.
  • Inverter IGBT Module Kits: Replacement semiconductor switches for your specific ACS880 frame size (e.g., Frame R1 through R9 or drive modules for larger frames).
  • Internal Current Transducers / Hall Sensors: Replacement sensors responsible for monitoring U2, V2, and W2 current channels.
  • Main Control Unit (BCU or ZCON board): In cases where signal processing electronics are degraded.

FAQ

Q: Can I run my ACS880 without a motor connected to check for Fault 3381?

Yes. However, by default, the drive will instantly trip on Fault 3381 if it detects zero current across the phases. To test the drive's voltage output without a load connected, go to Parameter Group 31 and configure parameter 31.19 Motor phase loss to "No action" or "Warning." Be sure to restore this setting to "Fault" once testing is complete.

Q: I only get Fault 3381 during rapid acceleration. Why is this happening?

This is typically caused by marginal resistance problems or a breakdown in cable/motor winding insulation. As the drive draws more current to run at higher speeds or dynamic ramps, the high current creates a voltage drop across loose terminations or triggers a brief insulation leakage bypass, tripping the drive. Check your acceleration ramp times and re-inspect crimps and terminations.

Q: Does a loose ground wire cause Fault 3381?

No. A loose ground wire or generic ground leakage typically registers as an Earth Fault (Fault 2330) or a short circuit. Fault 3381 is specifically looking for an open path or major unbalance in the three phase-to-phase current lines flowing through U2, V2, and W2.

Q: Why is my ACS880 tripping on output phase loss when using a very small motor?

If the physical motor is much smaller than the drive's nominal capacity, the currents drawn by the motor may fall below the lowest measurement limits of the drive's built-in current sensors. The drive interprets this low current as a broken wire or open path. For tiny test motors, change parameter 31.19 to "No action" or use a correctly sized drive matches for the motor's full-load amperage.

Shop the parts in this guide

Browse in-stock inventory for the products covered by this article.

Need a specific part?

Send us your part numbers — we'll respond the same business day with pricing and availability.

Are you an Electrical Distributor?Learn more about our distributor program

PALM Parts Solution sells used surplus products. PALM Parts Solution is not an authorized distributor, affiliate, or representative for the brands we carry. Products sold by PALM Parts Solution come with PALM Parts Solution's 1-Year Warranty and do not come with the original manufacturer's warranty. Designated trademarks, brand names and brands appearing herein are the property of their respective owners. This website is not sanctioned or approved by any manufacturer or tradename listed.

Read full disclaimer →