In short
Is your Allen-Bradley PowerFlex 40 displaying an F38 Fault? This guide covers the common causes behind the Phase U Short and details step-by-step troubleshooting to get it fixed.
Overview
The F38 fault code on an Allen-Bradley PowerFlex 40 drive indicates a Phase U Short circuit condition. This means the drive has detected an excessive, uncontrolled current spike or a low-resistance path to ground or another phase on the Phase U (T1) output terminal. When this occurs, the drive's internal control board immediately disables the inverter section output bridge to protect both the power semiconductors (IGBTs) and the connected motor from catastrophic failure.
Symptoms
When a PowerFlex 40 experiences an F38 fault, you will typically observe the following symptoms on the plant floor:
- Immediate Trip upon Run Command: The drive may display the F38 fault the exact millisecond a start or run command is initiated.
- Persistent Red LED: The red "Fault" status indicator on the VFD interface unit remains solidly lit.
- Intermittent Tripping at Specific Hertz: In some cases, the drive starts normal operations but trips abruptly as it ramps up or under high mechanical loads.
- Motor Disengagement: The motor coasts to a complete stop instantly without following normal deceleration ramps.
- Fault Cannot Be Cleared: Reset attempts (via keypad, control terminal digital inputs, or power-cycling) either fail immediately or the code returns as soon as the IGBTs attempt to modulate.
Possible Causes
An F38 error is rarely a random glitch. It points to a direct physical or electrical fault within one of these areas:
- Damaged Motor Cable Insulation: The cable running from the VFD output terminals to the motor terminal box has chafed, cracked, or melted insulation, causing Phase U to short to the grounded metallic conduit or to Phase V/W.
- Shorted Motor Windings: The insulation within the motor's Phase U stator winding has degraded due to heat, age, or voltage spikes, creating a phase-to-phase or phase-to-ground path.
- Moisture or Conductive Pollution: Water, oil, cutting fluids, or metallic dust have entered the motor conduit body or terminal box, bridging Phase U to the frame.
- Shorted Output Transistor (IGBT): The internal silicon-controlled rectifier or IGBT for Phase U inside the PowerFlex 40 power module has failed closed (shorted circuit).
- Excessive Output Cable Capacitance: High capacitive leakage current to ground, commonly found in extremely long, unshielded motor cabling runs without an output reactor.
- Faulty Drive Current Sensing Circuitry: Failure of the internal current sensor (Hall Effect transducer) or signal conditioning board on the VFD power card, incorrectly flagging a normal current draw as a short.
Step-by-Step Troubleshooting
Use these structured diagnostic steps to isolate the source of the F38 fault safely.
Step 1: Isolate Power and Perform LOTO
Before working on electrical cabinets or touching VFD output terminals, disconnect all incoming three-phase power. Exercise Lock-Out/Tag-Out (LOTO) protocols. Wait at least 5 to 10 minutes for the PowerFlex 40's DC bus capacitors to discharge completely. Verify zero voltage across terminals DC+ and DC- with a high-quality multimeter set to DC voltage.
Step 2: Perform the Static Diode / IGBT Test
Determining whether the drive itself is blown before checking the motor can save hours of panel disassembly. You will test the internal freewheeling diodes on the IGBT output bridge of the PowerFlex 40 using your digital multimeter's Diode Test Mode.
- Disconnect the motor leads from the VFD terminals
U/T1,V/T2, andW/T3entirely. Keep the wires suspended in the air to prevent false ground paths. - Place your multimeter's Red (Positive) probe on the
DC-terminal (found on the power terminal strip). - Touch the Black (Negative) probe to
U/T1, thenV/T2, and thenW/T3. You should see a standard forward diode drop of approximately 0.3V to 0.6V on all three terminals. They should be closely matched. - Now, reverse the configuration: Place the Black (Negative) probe on the
DC-terminal, and the Red probe onU,V, andW. The meter should read Open Loop (OL) or infinite resistance on all three. - Next, place the Black (Negative) probe on the
DC+terminal. - Touch the Red (Positive) probe to
U/T1,V/T2, andW/T3. Again, look for a standard diode drop of 0.3V to 0.6V across all three channels. - Reverse this: Place the Red probe on
DC+and the Black probe onU,V, andW. You must read Open Loop (OL).
Interpreting the Results: If your multimeter measures 0.000V or extremely low ohms (close to zero) on Phase U in both directions during this test, the internal Phase U IGBT is shorted. The PowerFlex 40 base unit must be replaced.
Step 3: Test the Motor Cabling with an Insulation Tester (Megger)
If the drive's internal IGBTs pass the diode test, the issue is downfield. Do not use a standard multimeter to test the motor cabling; standard multimeters operate on low DC voltage (typically 9V), which cannot detect insulation breakdowns that occur under dynamic medium voltages.
- Ensure the motor cables remain disconnected from the VFD.
- Set your insulation tester to 500V or 1000V DC (depending on the motor/cable rating; 500V is standard for 230/460V systems).
- Attach the ground lead of the tester to the main panel ground bus or conduit.
- Apply the test probe to the Phase U wire (originally connected to T1) and run the test. Compare this reading against Phase V and Phase W wires.
- A reading below 10 Megohms (MΩ) indicates severe cable insulation degradation. A reading at or near 0 MΩ means a hard short to ground.
- Next, test phase-to-phase insulation by connecting the leads to Phase U and Phase V, and then Phase U and Phase W. Insulation values should be exceptionally high (ideally >100 MΩ).
Step 4: Isolate and Test the Motor Separately
If testing in Step 3 yields a low insulation reading, you must determine whether the fault resides in the run of cable or the motor assembly.
- Locate the motor junction box at the actual machine.
- Unhook the connections inside the box, separating the incoming field cabling from the internal motor stator leads.
- Repeat the insulation resistance check (Megger test) directly on the motor terminal leads (U to ground, V to ground, W to ground, and phase-to-phase).
- If the motor stator windings test clean (>100 MΩ), the field cable run has been compromised. Replace the structural cable between the enclosure and the motor.
- If the motor stator fails, the motor must be removed for rewinding, baking to clear moisture, or total mechanical replacement.
Step 5: Check for Environmental Moisture and Carbon Tracking
Inspect the inside of the motor terminal box. Look for pooled condensate, mineral deposits, or black carbonized pathways across the terminal blocks (tracking). Moisture bridges Phase U to ground or adjacent terminals quite easily, resulting in a sudden F38 fault upon starting.
Step 6: Test the Drive Under No-Load Conditions
If both the drive's output diodes and the motor/cabling setup test perfect, run an isolated dynamic test of the VFD:
- Keep the motor cables fully disconnected from VFD terminals
U/T1,V/T2, andW/T3. - Turn off any open-phase protections in the drive parameters if necessary (Refer to Parameter
A098or sensor checks, though some PowerFlex drives permit running without a load by default for testing). - Apply control power to the drive and trigger a manual running state.
- Measure the output voltage across the empty terminals
UtoVandUtoWwith a true-RMS multimeter. The output phases should show balanced, climbing voltages as the drive ramps in frequency. - If the drive faults out on F38 with no load/no cables attached, the internal current monitoring transducers or control boards are defective, necessitating drive replacement.
Recommended Actions
Depending on what your troubleshooting reveals, take the following mitigation steps:
- If the drive is shorted (Step 2 failure): Procure a replacement PowerFlex unit. Do not attempt component-level repair on low-horsepower drives, as matched-semiconductor repair without specialty load-testing equipment poses a safety risk.
- If the cable has failed (Step 3 failure): Pull new, high-performance VFD-rated shielded cable through your conduits. Ensure shielding is terminated with 360-degree ground clamps at the drive enclosure to shunt high-frequency capacitive noise away from Phase U circuit pathways.
- If the motor housing is contaminated (Step 4/5 failure): Thoroughly clean, dry, and reseal the motor junction box. Replace dry/decaying terminal blocks and implement a condensation heater or drain valves in humid environments.
- If cable runs are long (>50 feet / 15 meters): Add a 3% impedance load reactor inline between the VFD and the motor to suppress capacitive charging currents that can trip the high-frequency peak current threshold of Phase U.
Recommended Replacement Parts
To confidently resolve this fault and secure permanent uptime, consider replacing older or compromised power equipment with these parts:
| Part Type | Recommended Specification | Function |
|---|---|---|
| Replacement VFD | Allen-Bradley PowerFlex 40 (or migration to PowerFlex 525) | Complete unit replacement for damaged IGBT power bridges. |
| Cabling | VFD Shielded Power Cable (e.g., Southwire or Belden) | Provides physical protection and limits transient capacitive currents in Phase U. |
| Output Line Reactor | 3% Impedance Load Reactor (harmonized to motor HP/Amps) | Smooths output current waveforms and prevents nuisance trips due to cable length capacitance. |
| Stator/Motor Protection | Shaft grounding rings / Insulated motor bearings | Protects standard AC induction motors from premium VFD micro-arcs. |
Related Articles
- /knowledge/replacement/powerflex-40-to-powerflex-525-migration-guide
- /knowledge/compatibility/matching-line-reactors-to-allen-bradley-vfds
- /knowledge/guide/how-to-test-vfd-igbts-with-multimeter
FAQ
Q: Can I run my VFD with the F38 fault temporarily bypassed or disabled?
No. The F38 fault limits raw, short-circuit currents. Disabling or bypassing this hardware protection mechanism (even if somehow forced in parameters) would instantly result in violent localized thermal failure of the silicon transistors, destroying the power module, melting surrounding wiring, and presenting a severe arc hazard inside your control panel.
Q: Why does my drive only display F38 after running for 5 to 10 seconds?
This is typically caused by thermal/dynamic insulation breakdown. When stationary and tested cold with a simple multimeter, the motor windings and cabling show standard resistance. However, once running, high voltage pulses (PWM) build up heat and mechanical stress, triggering a short-to-ground or phase-to-phase arc only after several seconds of active operation. A Megger test is crucial for detecting this.
Q: Does Phase U short always mean the drive itself is ruined?
Not at all. In roughly half of industrial calls, the root cause is external to the drive (chafed wire inside a wet conduit, terminal box condensation, or damaged motor stator windings). Always complete the isolation diagnostic steps before purchasing a replacement drive.
Q: What is the difference between F38, F39, and F40 on a PowerFlex 40?
They represent the same overcurrent-sensing logic but are isolated to different physical output terminals: F38 identifies Phase U (T1), F39 represents Phase V (T2), and F40 designates Phase W (T3). Each points to a localized fault on that specific physical leg.
Shop the parts in this guide
Browse in-stock inventory for the products covered by this article.
